need for emergency lighting
When the supply to the normal lighting of a premises fails, emergency lighting shall be required.
Emergency escape lighting
When the supply to the normal lighting or parts of the normal lighting to occupied premises fails, emergency escape lighting shall be provided:
a) to indicate clearly and unambiguously the escape routes,
b) to provide illumination along such routes to allow safe movement towards and through the exits provided,
c) to ensure that fire alarm call points and fire fighting equipment provided along escape routes can be readily located,
d) to provide sufficient lighting to enable the emergency services to conduct a search and rescue in the event of an incident,
e) to provide lighting for building re-occupation.
Non-maintained, combined and maintained emergency luminaires shall operate in the event of failure of a normal lighting final circuit. In all cases, arrangements shall be made to ensure that local emergency escape lighting will operate in the event of failure of normal supply to the corresponding local area.
illumination for safe movement
The safe movement of persons along escape routes towards and through the exits provided to a place of safety depends upon the illumination and the ability to see hazards, changes of level and direction.
It is recommended that all potential obstructions or hazards on an escape route should be light in colour with contrasting surround. Where the design departs from the above, it will be necessary to compensate for such departures. Escape routes shall be kept clear of unnecessary obstructions at all times and shall not be used as storage areas.
Minimum illuminance
Defined escape routes
For escape routes up to 2 m in width, the horizontal illuminance on the floor along the centre line of an escaperoute shall be not less than 1 lux and the central band consisting of not less than half of the width of the route shall be illuminated to a minimum of 50% of that value.
NOTE Wider escape routes can be treated as a number or 2 m wide strips or be provided with open area (anti-panic) lighting (see clause 4.2.1 of I.S. EN 1838:1999).
Undefined escape routes (open areas)
The horizontal illuminance shall be not less than 0,5 lux at the floor level of the empty core area which excludes aborder of 0,5 m of the perimeter of the area (see clause 7.6.8 below, I.S. EN 1838:1999 clause 4.3.1 and,I.S. EN 50172:2004 clause 4.4.).
Response time
The emergency lighting specified in this Standard shall provide full luminance within 5 s of the failure of the normal lighting supply.
High risk task area lighting specified in this Standard shall provide the full required luminance permanently or within0,5 s of the failure of the normal lighting supply depending upon application.
Design conditions
The recommended illuminances that are specified as a minimum, i.e. 0,5 lux or 1 lux, shall be regarded as the lowest value acceptable during the rated discharge period and due to the effects of the system ageing (see I.S. EN 1838:1999).
In designing a system allowance shall be made for all of the relevant factors including reduction in voltage, voltage drop in the system wiring, lamp ageing and the accumulation of dirt and dust.
Requirements on the measuring of illuminance of emergency lighting are given in Annex A.
Uniformity of illuminance
The ratio of the maximum to the minimum illuminance shall be not greater than 40:1 along the centre line of the escape route.
Glare
Disability glare shall be kept low by limiting the luminous intensity of the luminaires within the field of view.
All Open Areas (Panic Areas) must have a minimum illumination of 0.5 lux
All exit doors and exit routes must have adequate signage to direct people safely from the building.
Areas deemed to be of 'high risk' must be illuminated to 10% of normal light or to an illumination level of at least 15 lux
design guide lines
Please review our Emergency Lighting Design Guide Lines >>>